>OFFICE SPECIFICATIONS >RETAIL SPECIFICATIONS
|
| WALL | All demising walls, exterior walls, columns and tenants demising partitions are taped and sanded drywall on metal studs.
|
| STOREFRONT | Supply and install interior/exterior window if any or storefront in accordance with the Landlord's Architect’s design.
|
| FLOORS | Steel troweled concrete.
|
| PLUMBING | Main drain (underslab) and main water supply pipe to the Unit shall be available for the connection by the Tenant.
|
| MECHANICAL SYSTEM | Energy conserving 4-pipe fan coil system (hot and chilled water sources supplied by Markham District Energy) combined with year round heating and cooling at a rate of approx. 1 Ton/400 square feet of leased premises. Individual temperature control zones 1 per approximately 1000 square feet. All HVAC distribution by Tenant.
|
| POWER | 600 volt (60, 100 up to 400 amp) electrical service terminating at a disconnect switch in the main electrical room shall be provided by the Landlord. The Landlord's Electrical Engineer shall approve the electrical service for required usage.
|
| SPRINKLER SYSTEM | Sprinkler line and head to meet NFPA13 code requirements shall be provided to the Leased Premises (unit).
|
| GAS | Main gas service line for restaurant to meter location outside of the unit approved by Enbridge Gas (Note: All restaurants should use gas fired equipment for cooking only at a cost to themselves.).
|
| METERS | Landlord to provide individual sub- metering system to meter all electrical consumption for the Tenant’s leased premises at the Tenant’s expense. The Landlord at the Tenant’s cost will install sub-metering as required for restaurant use or any Tenant with above normal usage of water and HVAC. |